4 Zone Fire Alarm Panel Ravel
$56.1
$107.15
Technical Specification: RE-104 Conventional Type Fire Alarm Panel.Primary Power: 120 – 220VAC , 50 HzStandby Power: 24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).Quiescent current : 55mACommon Relays : Type : Form CNo of Relays : 3Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @125VAC.Power Factor : 1Charging Circuit: Charging Voltage 28.2V, ±0.5VCharging Current 0.5 A (Max.).Notification Appliance Circuits: Class B wiring Operating Nominal Voltage : 24VDC Current for NACs : 0.6 Amp End-Of-Line Resistor : 4K7, 1/4 watt Initiating Device Circuits (Zone Circuit) All zones are Class B wiring Normal Operating Voltage : 14- 21 VDC Alarm Current : 15 – 30mA Short Circuit Current : 42mA Maximum Loop resistance : 50 ohms Maximum End-Of-Line Resistor : 4.7K, 1/4watt Standby Current : 6.8mA (2.4mA for Detectors)